L26491 PRELIMINARY REPORT GW192.docx
《L26491 PRELIMINARY REPORT GW192.docx》由会员分享,可在线阅读,更多相关《L26491 PRELIMINARY REPORT GW192.docx(12页珍藏版)》请在冰点文库上搜索。
L26491PRELIMINARYREPORTGW192
PRELIMINARYREPORTOFSURVEY
LandRigGW192
Preparedfor
GreatWallDrilling
PanjinChina
By
MODUSPECINTERNATIONAL(L)LTD
Dates:
19th–23rdJuly2012
4.0LISTOFRECOMMENDATIONS
Therecommendationsinthisreportaredefinedasfollows:
Criticalrecommendations
Criticalrecommendationsarebasedonshortcomingswhichmayleadtolossoflife,aseriousinjuryorenvironmentaldamageasaresultofinadequateuseand/orfailureofequipment.
Majorrecommendations
Majorrecommendationsarebasedonshortcomingswhichmayleadtodamagetoessentialequipmentorhaveadetrimentaleffectonthedrillingoperationasaresultofinadequateuseand/orfailureofequipment.
Minorrecommendations
Minorrecommendationsarebasedonshortcomingswhichmayleadtoasituationthatcontributestoanincidentortocircumstancesinwhichtherequiredstandardsofoperationarenotmet
DrawworksRecommendations:
5.1.1.1MajorInstallalarmfornowaterflowandhighbrakewatertemperatureondrawworksdiscbrakes
5.1.1.2MajorEnsuretoinstall“Y”strainerinsuctionsideifthebrakewatercoolingpumps.Withoutstrainersthecavityofthediscbrakescouldbeblockedwithdebris.
5.1.1.3MajorProvidemaintenancereportforallworkcarriedoutonthedrawworksduringrefurbishment.
5.1.1.3MinorReplacethetwopressuregaugesonthegearboxes.
DiskBrake(Universal)Recommendations:
5.1.2.1.1CriticalDismantleallbrakecallipersandserviceaspermanufacturesspecification.Cleanbrakediscforallgreaseanddirt.Verifybrakediscisnotundersize(worn)
5.1.2.1.2CriticalVerifywithmanufacturermaximumdurationofserviceforthesafetycallipers.Thespringmayhavetobechangedafter6yearsinservice.Somemanufacturesrecommend12monthlychangeout
5.1.2.1.3CriticalVerifycorrectpre-chargeintheHPUaccumulatorbottles.
5.1.2.1.4MajorRepairallhydraulicleaksandreplaceoldhydraulichoses.
5.1.2.1.5MajorProvidemaintenancereportforthediscbrakes
SwivelRecommendations:
5.4.1.1CriticalVerifythatthethreadedconnectionoftheswivelhasbeeninspectedforcracksandthattherighasavalidinspectionreportavailable.APIRP8BTable1
5.4.1.2CriticalVerifythattheswivelyokehasundergonetherequiredNDTinspectionforcracksasperAPIRP8B.Validinspectionreportsmustbeonfileattherigsite.
TravellingBlockRecommendations:
5.8.1.1CriticalInstallsuitablepadeyeunderthecrownblockwithSWLcapableofhangingthetravellingblockandhook.Thisisforsafetyhangofflineduringslipandcutofdrillingline.
5.8.1.2MajorVerifythatthehighloadbearingareasofthetravellingblockareregularlyNDTinspectedasperAPIRP8B.(6-montlyand5-yearly).APIRP8Bsection5Table1.
HookRecommendations:
5.9.1.1CriticalProvidefullNDTinspectionreportsforthehookandthatithasbeeninspectedasAPIRP8Bsection5table1.
DrillingInstrumentationRecommendations:
5.10.1.1MajorVerifyallinstrumentationiscalibratedsuchasRPMoftherotarytable,MDloadindicator,flowmeter,mudpumppressuregauges,etc.
DerrickRecommendations:
5.11.1.1CriticalInstallsuitablebumperblockunderthecrown.IfbumperblockismadeoftimberheavydutywiremeshmustbeinstalledaroundtheblockAPIRP54section9.2.16
TuggersandSheavesRecommendations:
5.13.1.1CriticalProvideengineeringcalculationforthetuggerfoundationverifyingSWLforthetwo5tondrillfloortuggerwinches.
5.13.1.2MajorMarkclearlythewinches"NOTFORMANRIDING"
MUDSYSTEM
MudAgitatorsRecommendations:
6.8.1.1CriticalNumberallagitatorsinaccordancewithoilfieldrecommendedpractices.Numberoneistheoneclosesttothedriller
6.8.1.2CriticalNumberallremotestart/stoponthemudtanksinaccordancewithagitatorandMCCpanel.
FlowLineSystemRecommendations:
6.9.2.1.1MajorEnsuretheworkingareaaroundthegumboboxissufficientforpersonnelsocleaningandmaintenancecanbedoneinasafemanner
BOP-HandlingEquipmentRecommendations:
7.6.1.1CriticalStripdownthetwotrolleybeamcranesforinspectionandreplaceworn,defectparsasrequired.
POWERPLANT
CaterpillarEnginesRecommendations:
9.1.2.1.1CriticalRepairemergencyairintakeshutoffvalvesongeneratorengines1and2
9.1.2.1.2MajorInstallremoteshutdowndeviseforallfourRiggenerators.Oneemergencyshutdownbuttoninthedrillerscabin.
AirReceiversRecommendations:
9.3.1.1.1CriticalHavepressurereliefvalveonairreceivernumber1re-tested
9.3.1.1.2CriticalHavereliefvalveventlineextendedtonearthefloorforsafetyreason
ELECTRICALEQUIPMENT
AuxiliaryBrakeRecommendations:
10.1.1.1CriticalCompleteoverhaulofResistorbankandtest
10.1.1.2MajorRoutingofcables[flatbar/cabletray]oftheresistorbankawayfromdeckplate
10.1.1.3MinorMechanicalcleanup&paint
MainGeneratorRecommendations:
10.2.1.1MajorReplacesingleholecablelugswithdoubleholeones
10.2.1.2MajorInstallaudio/visualalarmunit&commissionthesame.
10.2.1.3MajorMechanicalcleanupofGenerators3/4/5
10.2.1.4MinorProvidecableidforpowercablesatbothends.
10.2.1.5MinorProvidepropersizedearthcableforallgeneratorscleanearthboss&protectwithgrease.
10.2.1.6MinorProvideidtagsforcableatbothends.
MainTransformer(3-Phase)Recommendations:
10.3.1.1MajorInstallvisiblewarningsignpostingonmain&lightingtransformersenclosure
10.3.1.2MajorRoutecablestouchingdeckonaraisedflatbar/cabletray.
10.3.1.3MajorTheOEMhasprovidedoubleholearrangementonthemaintransformerbussoprovidedoubleholecablelugswithstdsizebolts&torquetoOEMspecifications.
10.3.1.4MajorReplaceearthcablewithpropersized,removerustonearthbossandapplycorrosionprotectiongrease.
10.3.1.5MinorMechanicalcleanup&painttouchupoftheinsideoftransformersenclosure
10.3.1.6MinorProvidelubricationonhinges&latchesofTransformerenclosuredoorforeasyquickopening.
10.3.1.7MinorCarryoutThermalinspectionofbusbars&connection&logthesame.
10.3.1.8MinorProvideIdtagsforallcables
Converters(SCRandVariable-FrequencyDrives)Recommendations:
10.4.1.1MajorGroundconnectioncrosssectiongreaterorequaltosupplyconnectionforsuppressionofradiointerferencenoise.OEMREQUIREMENTS
10.4.1.2MajorUsescreenedpower&controlcablesbetweenconverteroutput&motorThescreenmustbegroundedatbothend.OEMREQUIREMENTS
10.4.1.3MinorCarryoutTHERMALINSPECTIONofbusbars&connection&logresultsforfuturereference.
MainSwitchboardRecommendations:
10.5.1.1CriticalProvideCurrentinjectiontestreports
10.5.1.2MajorProvidegroundfaultdetectionsystem.
10.5.1.3MinorCarryoutthermalinspectionandlogforfuturereference
10.5.1.4MajorSupply&mountsafetyhook&Highvoltagerubberglovesinbothmainswitchboardcabins.
ACMotorsInsulationTestRecommendations:
10.8.1.1.1MinorProvideinsulationtestresultsofallmotors
MCCPanelsRecommendations:
10.9.1.1MajorRemoteoperationstarterstobeprovidedwithidtagswarningsignstobemountedinbothMainswitchboardcabins.
10.9.1.2MajorProvideloadanalysis;Shortcircuitcalculations&Tripco-ordinationstudyreport
10.9.1.3MinorCarryoutthermalinspection&logforfuturereference
LightingSystem(Main)Recommendations:
10.10.1.1MajorRectify&supportallcablesatthebottomofMainlightingDB
10.10.1.2MajorAddoneadditionalceilinglightfixturetobothmainswitchboardcabinsandgeneratorcabins.
10.10.1.3MajorAllpolelightsinstalledonthedrillfloor,shaleshaker&mudtankswillhavetobeprovidedwithadditionalsupporttomakethemrigid.
10.10.1.4MajorProvidelightfixtureoutsideallcabindoors.
10.10.1.5MajorMechanicalcleanup5noexlightsondrillfloor&replacePGwithexglands
10.10.1.5MinorIdtagthecompletelighting&smallpowersystem.
LightingSystem(Emergency)Recommendations:
10.11.1.1MajorProvideadditionalbatterybackuplightsinGenerator/Machineryroom
10.11.1.xMajorInstallallbatterybackuplightscorrectlyinrightlocation
10.11.1.xMinorProvideEsignonallemergencylights.
ElectricalOutletsandPortableEquipmentRecommendations:
10.12.1.1CriticalProvideResidualcurrentcircuitbreakerforallelectricaloutletmeantforhandtools.
Batteries,BatteryChargersandUPSRecommendations:
10.14.1.1CriticalProvidebatterychargerforgeneratorno5
10.14.1.2MajorProvidenew24v/30AUPSforGenerator1,3&4
EarthingandEarthBondingRecommendations:
10.18.1.1MajorProvidepropercolorcoded&sizedearthbondingcables
MiscellaneousItemsRecommendations:
10.20.1.1MajorOrganizeandprovidetechnicaldrawingsandmanualstocoverallrigequipmentsandfacilitatetrouble-shooting.
SAFETYEQUIPMENT
AutomaticFireDetectionSystemRecommendations:
11.1.1.1.1CriticalEnsureallbuildingsareinstalledwithsmokedetectors.Smokedetectorsshouldbehardwired.
PortableExtinguishersandFire-FightingEquipmentRecommendations:
11.1.4.1.1CriticalMachineryspacesanddieseltankstationsaretobeequippedwithextinguisherssuitableforoilfires.50%oftheseshouldbeofthefoamtype.
11.1.4.1.2CriticalInstallsignabovefireextinguishersclearlymarkingthelocationofeachfireextinguisher.
11.1.4.1.3MinorInworkingareasthereshouldalwaysbeanextinguisherathandwithin10metres,preferablymountedinabracket,notloosestanding,andprotectedfromtheweather
11.1.4.1.4MinorExtinguishersaretobenumberedandrecorded.Inspectthemonamonthlybasis.
11.1