IndonesiaT.J.AWARAWAR2×350MWPowerPlantProject
CommissioningProcedureof
150kVSwitchyardandAuxiliaryPowerSectionEnergizing
150KV升压站及厂用电部分送电调试程序
No.:
P-E07
CUSTOMER
PT.PLN(PERSERO)
PT.PLNJASASERTIFIKASI
EPCCONTRACTORSCPJO
NEPRI
NortheastElectricPowerResearchInstituteCo.,Ltd
(LiaoningDongkeElectricpowerCo.,Ltd)
Rev.
Description
Prepared
Checked
Approved
Date
1
2
3
4
5
CompilationBasisoftheGuidance
1.IndonesiaT.J.AWARAWAR2×350MWpowerplantprojectcommissioncontract
2.DesigndiagramsofChinaUnitedEngineeringCorporation
3.Thedesignspecifications,operationandmaintenanceinstruction,assemblemanualandcorrelationdiagrampapermaterialofrelevantmanufactories
4.Contractgivenbyproprietorandminuteofrelevantmeeting
编制依据
1.印尼TanjungAWAR发电站2×350MW机组工程调试合同
2.中国联合工程公司设计图纸
3.各设备厂家的设计说明、运行维护手册、装配手册以及相厂家的关图纸文件资料。
4.业主提供的合同及相关会议纪要
Catalogue
NEPRI1
1.General1
2.Objective2
3.Energizingrange2
4.Precondition3
5.Energizingofmobiletransformer5
6.Energizingof150kVswitchyard5
7.EnergizingofSST5
8.Energizingof6kVcommonsection6
9.Energizingof6kVworkingsection6
10.Safetymeasure7
11.Systemdiagram13
1.General
2×350MWcoal-firedgeneratingunitsshallbeinstalledinT.J.AWARAWARpowerplant,whichisprovidedwith150kVdistributionequipment.FourcircuitsareledoutfromsuchequipmentandthenconnectedwiththeIndonesia150kVsystem.A3/2CBwiringmodeisusedfor150kVdistributionequipment.Twogeneratingunitsaresteppedupviaamaintransformerandthenswitchedin150kVbusbar.Theentirepowerplantisprovidedwithonestartup/backuptransformerasthestartupandbackuppowersupplyfortheunitsofthepowerplant,whichisconnectedviathebusbarof150kVdistributionequipment.
150kVdistributionequipmentisarrangedoutdoorsinamiddle-sizedform,whileCBsareduallyarrayed.Eachstringofincomingandoutgoinglinecircuitoccupies2intervals.ThemaintransformerandtheoutgoinglinesetinCircuit1formonecompletestring,andthenthestringisarrangedintwointervals;theincominglineofthestartup/standbytransformerandtheoutgoinglinesetinCircuit1formonecompletestring,andthenthestringisarrangedintwointervals;themaintransformerinCircuit1andtheurbansupplytransformeroutgoinglineaswellastransformersarearrangedintheintervalofacompletestringandoccupiestwointervals.Bothendsofthebusbarareprovidedwithabusbarearthingswitch.
Two350MWturbogeneratorunitsareswitchedin150kVdistributionequipmentinaconnectionunitformofgenerator-transformerbank.Theoutgoingendofthegeneratorandtheoutgoingbushingattheendofaneutralpointareequippedwithfourgroupsofcurrenttransformers;theoutgoingendofthegeneratorisequippedwiththreegroupsofpotentialtransformersandonegroupofsurgearresters;theneutralpointofthegeneratorisearthedviathesecondaryresistanceofasinglephaseearthingtransformer.Thegeneratorandthemaintransformerareconnectedbyusingcontinuousenclosure-typeisolatedphasebusbar.Ahighvoltagestationtransformerandanexcitationtransformerareconnectedfrombetweenthegeneratorandthelowvoltagesideofthemaintransformer.Astaticself-shuntsystemisusedfortheexcitationofthegenerator.
Twovoltagelevelsof6.3kVand400/230Vareusedinthestation-servicepowersystem.Theratedvoltageofamediumvoltageelectricmotoris6kV,andtheratedvoltageofalowvoltageelectricmotoris380V/220.2×350MWcoal-firedgeneratingunitsareinstalledinT.J.AWARAWARpowerplant.Accordingtotheloadstatisticsofelectricalequipmentinallprocesssystemsofthepowerplant,eachgeneratingunitisprovidedwithonehighvoltagestationtransformer,whichisusedtosupplypowerforelectricalequipmentfortheunitplant.Thepowersupplyatthehighvoltagesideofthehighvoltagestationtransformerareconnectedthroughabranchfromanenclosedbusbarbetweenthegeneratorofthegeneratingunitandthemaintransformer,whilethepowersupplyatthelowvoltagesideareconnectedwith6kVswitchgearofthegeneratingunitbyusingcommonenclosurebusbar.Themainbuildingisprovidedwith6kVcommonbusbarsection.Boththepowerforthecommonsystemofthepowerplantandtheproductionauxiliarysystemaresuppliedby6kVcommonsection.Thepowersupplyforthe6kVcommonsectionisconnectedviaastartup/backuptransformer,whoselowvoltagesideisconnectedwiththeswitchgearforthe6kVcommonsectionbyusingcommonenclosurebusbar.
Maintechnicalparametersareasfollows:
Start-up/Standbytransformer
Model:
SFFZ-50000/150
No-loadloss:
40kW
Ratedvoltageratio:
1508×1.25%/6.3kV
Loadloss:
211.5kW
Ratedpower:
50/31.5-31.5MVA
No-loadcurrent:
0.1%
Ratedfrequency:
50Hz
Soundlevel:
75dB
Numberofphases:
Threephases
Partialdischarge:
100pC
Voltageregulationmode:
OLTC
Earthingmodeofneutral:
Directly(H.V.)/Resistanceneutralgrounding(L.V.)
Connectionsymbol:
YN,yn0-yn0+d11
Coolingtype:
ONAN/ONAF
Impedancevoltage:
21%
2.Objective
2.1Checktheoperationperformanceofrelevantprimaryequipmentsunderratedvoltage.
2.2Checktherelevantprotection,measurement,controlandsignalloop.
2.3Supplypowertoauxiliarypowersectionforunitcommissioning.
3.Energizingrange
Thepowerenergizingrangeoftheproposalisasfollowed(seethemainelectricalconnectiondiagram).Thewhole150kVswitchyardshouldbeenergizedbythemobiletransformer,andthenthepowerwouldbesentto6kVcommonsections,6kVworkingsectionsthroughthestartup/standbytransformer.Theenergizingequipmentsareasfollows:
a)Mobiletransformer
b)150kVswitchyard:
busbar,CB,DS,CT,PT,arrester
c)SST
d)6kVcommonsectionAandB
e)6kVworkingsection1Aand1B
Ifnecessary,adjustmentshouldbemadefortheenergizingproposalaccordingtothepracticalsituation.
4.Precondition
4.1Theinstallationandcommissioningofthesubstationprimaryequipmentintheenergizingrangeshouldbefinished.Theinspectionandacceptanceisqualified,andtheacceptancereportsarecomplete.
4.2Theinstallationandcommissioningofthestartup/standbytransformershouldbefinishedandtherelevanttestshouldbefinished.Alltheinspectionandacceptanceisqualified,andtheacceptancereportsarecomplete.
4.3Theinstallationandcommissioningofthe6kVsectionprimaryequipmentintheenergizingrangeshouldbefinished.Theinspectionandacceptanceisqualified,andtheacceptancereportsarecomplete.
4.4Thecharacteristictest,withstandvoltagetestandinsulationtestofalltheelectricalequipmentsshouldbequalifiedaffirmed.
4.5Therelevantprotection,control,measurementandsignalloopshavebeencommissionedandconfirmedqualified.
4.6Confirmthaton-loadtapchanger,coolingsystemandtemperaturemeasuringdeviceofrelevanttransformersareallingoodcondition,andthetapofthetransformersshouldbeattheratedposition.
4.7ThecommissionoftheCBprotectionandthetransformerprotectionshouldbefinished,andthetrippingtestshouldbeallright.Theinspectionandacceptanceisqualified,andtheoperationconditionisready.
4.8ThesettingvaluesofCBprotection,thetransformerprotectionandtheauxiliarypowerprotectionareallrightaccordingtothesettingvaluespaper.
4.9TheoperationstateofmobiletransformerCBisallright.
4.10ThecommissioningoftheNCS,DCSsystemshouldbefinished,aswellasthefunctiontest.Theoperationconditionisready.
4.11Inthe150kVswitchyard,thecommunicationdevice,firefightingdevice,illuminationdeviceshouldbecomplete,andthesafetypassagewayshouldbesmooth.
4.12Thefencingandwarningmarksinthe150kVsubstation,the6kVswitchgearroomandthetransformerareashouldbecomplete.
4.13Thefencing,ground,andilluminationoftransformersiteshouldbeallright.Andtheearthingoftransformerbodyisnoproblem.
4.14Duringtheenergizingtest,operatorsshouldbesentto150kVsubstation,the6kVswitchgearroomandthetransformersite.Monitortheoperationstationoftheequipment,andthecommunicationdeviceshouldbenoproblem.
4.15Fireproofingblockingforallthecablecabinetsshouldbefinished,andtheremustbeenoughfire-fightingequipment.
4.16Forthefirsttimeofthetransformerenergizingtest,putthefirefightingsystemintooperation.Ifthefirefightingsystemisnotready,afiretruckshouldbereadynearthetransformer.
4.17Thereshouldbeenoughfireextinguishersespeciallyforelectricaluseinthetransformerareaandtheswitchroom.
4.18Thephasesequenceofelectricalprimaryequipmentsshouldbeallright.
4.19TheDCpowersystemandUPSsystemshouldberunningnormally.
4.20Allthetestinstrumentsshouldbeready.
4.21ThesecondaryloopofCTandPTshouldbechecked.
4.22Themeteringsystemofrelevantequipmentshouldbequalified.
4.23Thegroundconnectionofelectricaldeviceshouldbeallright,andthegroundresistanceshouldbequalified.
4.24Thenamesandthenumbersoftheelectricalequipmentshouldbeclear.
4.25Thecommunicationdevice,firefightingdevice,illuminationdeviceshouldbecomplete,andthesafetypassagewayshouldbesmooth.
4.26The6kVcommonbusbartoUnit2shouldbedismantled,andtheremustbeenoughsafetymeasuresforisolationandinsulation.
4.27Theh.v.sideconnectionof#1,#2maintransformershouldbedismantled,andtheremustbeenoughsafetymeasuresforisolationandinsulation.
4.28Befor