AB增强冗余系统版本精
ReleaseNotes
ControlLogixEnhancedRedundancySystem,Revision16.81
RedundancyModuleCatalogNumbers
1756-RM,1756-RMXT
ControllerCatalogNumbers
1756-L61,1756-L62,1756-L63,1756-L63XT,1756-L64
CommunicationModuleCatalogNumbers
1756-CN2/B,1756-CN2R/B,1756-CN2RXT/B,1756-EN2T,
1756-EN2TXTTopicPageAboutThisRedundancyFirmwareBundle2CompatibleSoftwareVersions
3FactoryTalkViewSoftwareConsiderations
4AbouttheRedundancyModuleConfigurationTool
4Enhancements
5EnhancementswithRevision16.81
5EnhancementswithRevision16.80
5EnhancementswithRevision16.54
8CorrectedAnomalies
10CorrectedAnomalieswithRevision16.81
10CorrectedAnomalieswithRevision16.81
10CorrectedAnomalieswithRevision16.54
16KnownAnomalies
17Restrictions
19ApplicationNotes
22EtherNet/IPNetworksandRedundantSystems
22MinimumValuefortheWatchdogTime
22SynchronizingAfterDisqualification
22UsingaRedundantSystemandCIPEquipmentPhases
24UsingtheEquipmentPhase.StepIndexTag
24UsingUnitTags
26MultipleCIPDataServerswithOneFactoryTalkBatchServer26
Publication1756-RN650D-EN-E-February20102ControlLogixEnhancedRedundancySystem,Revision16.81
AboutThisPublication
Thesereleasenotesdescribeenhancements,correctedanomalies,andknownanomaliesspecifictoredundancysystemfirmwarerevision16.81.Informationnewly-addedtothisreleasenoteisindicatedbychangebarsliketheoneshowntotherightofthisparagraph.AboutThisRedundancyFirmwareBundle
Thisredundancyfirmwarebundleiscomprisedoffirmwarerevisionsforeachofthemoduleslistedinthistable.UpgradeFromAnEnhancedRedundancyRevision28StoreaProjecttoNonvolatileMemoryWhileYourProcessisRunning44AdditionalResources46TopicPageIMPORTANTOnlythemodulesspecifiedinthetablebelowcanbeusedintheenhancedredundancysystemandthisfirmwarerevision.Modulesthatarenotlistedinthetablearenotcompatiblewiththeenhancedredundancysystemandarenotsupportedbythisredundancyfirmwarerevision.Cat.No.ModuleDescriptionSeriesFirmwareRevision1756-CN2ControlLogixControlNetbridemoduleB20.0111756-CN2RControlLogixredundantControlNetbridgemoduleB1756-CN2RXTControlLogix-XTredundantControlNetbridgemoduleB1756-EN2TControlLogixEtherNet/IPbridgemoduleAny2.0071756-EN2TXTControlLogix-XTEtherNet/IPbridgemodule
Any
Publication1756-RN650D-EN-E-February2010
ControlLogixEnhancedRedundancySystem,Revision16.813Thefirmwarebundlecanbedownloadedat:
.ItisidentifiedasV16.81EnhClxRed.CompatibleSoftwareVersionsUsetheseversionsofsoftwarewiththisredundancyfirmwarebundle.SoftwareVersionFactoryTalkServicesPlatform2.10.01(CPR9,SR1(1(1UsethemostrecentFactoryTalkServicesPlatformPatchRoll-upwith
thisredundancyfirmwarerevision.Forthemostrecentpatchroll-up,
seeRockwellAutomation’sKnowledgebaseAnswerID56184,
accessibleat:
.
FactoryTalkAlarmsandEvents2.10.00(CPR9
FactoryTalkBatch10.00.26
FactoryTalkViewSiteEdition5.00.00(CPR9
RedundancyModuleConfigurationTool6.2.10
RSLinxEnterprise5.17(CPR9,SR1(2
(2SeeFactoryTalkViewSoftwareConsiderationsonpage4foruse
considerations.
RSLinxClassic2.54(3
(3IfyourredundantsystemiscomprisedofControlLogix-XTmodules
placedina1756-A5XTchassis,RSLinxClassicsoftware,version2.55,
orlater,isrequired.
RSLogix500016
RSNetWorxforControlNet8.00(CPR9,SR1
1756-L61ControlLogix5561controllerAny16.811756-L62ControlLogix5562controller1756-L63ControlLogix5563controller1756-L63XTControlLogix-XTcontroller1756-L64ControlLogix5564controller1756-RMControlLogixredundancymoduleA2.051756-RMXTControlLogix-XTredundancymoduleCat.No.ModuleDescriptionSeriesFirmwareRevision
Publication1756-RN650D-EN-E-February20104ControlLogixEnhancedRedundancySystem,Revision16.81
FactoryTalkViewSoftwareConsiderationsFactoryTalkViewsoftwareisrequiredforuseonlywiththesehuman-machine-interfaces(HMIs:
•PanelViewPlusterminal•VersaViewindustrialcomputerrunningaWindowsCEoperatingsystem•RSViewSupervisoryEditionsoftwareAbouttheRedundancyModuleConfigurationTool
TheRedundancyModuleConfigurationTool(RMCTisrequiredforusewiththe1756-RMmodule.UsetheRMCTto:
•configureredundancysystemparameters.Forexample,toconfiguretheAuto-Synchronizationparameter.•viewredundancysystemeventlogswhentroubleshootingyoursystem.TheRMCTisnotpackagedwiththisredundancyfirmwarerevision.RSLinxClassicsoftwareincludestheRMCT,however,itisnotlikelytobetheversionthatiscompatiblewiththisfirmwarerevision.CompletethesestepstoobtainthecompatibleversionoftheRMCT.1.AccessKnowledgebaseAnswerID29511(availableat:
.2.Downloadtheversionlistedforthisredundancyfirmwarerevision.3.OpentheexecutablefileandusetheInstallationWizardtoinstallthetool.ForinformationaboutcheckingtheversionofyourRMCT,seeUpgradetheRedundancyModuleConfigurationTool(RMCTon.
IMPORTANTIfyouareusingFactoryTalkViewSiteEditionsoftware,installtheRSLinxEnterpriseHOTFIX.TheHOTFIXimprovestheEtherNet/IPswitchovertime.Formoreinformation,seeKnowledgebasedocumentR154640079.ToaccessRockwellAutomation’sKnowledgebase,goto.
Publication1756-RN650D-EN-E-February2010ControlLogixEnhancedRedundancySystem,Revision16.815
EnhancementsTheseenhancementsareprovidedwithenhancedredundancyfirmware
revisions16.81,16.80,and16.54.
EnhancementswithRevision16.81
Thisenhancementisprovidedwithstandardredundancyfirmwarerevision
16.81.
EnhancementswithRevision16.80
Theseenhancementsareprovidedwithenhancedredundancyfirmware
revision16.80.SystemComponent
Enhancement1756-L61,1756-L62,1756-L63,1756-L63XT,1756-L64ThefalseexecutiontimeofAdd-OnInstructionshavebeenimproved.Withpreviousrevisions,thefalseexecutiontimeofanAdd-OnInstructionwasdependentonthenumberofparameters(input,output,andinoutconfiguredfortheinstruction.Themoreparametersconfigured,thelongerthe
falseexecutiontimeoftheAdd-OnInstruction.
Withthisrevision,thefalseexecutiontimeofanAdd-OnInstructionisnowconstantifascanfalseroutineisnotcreated.TodeterminethefalseexecutiontimeofAdd-OnInstructionsbasedonyourcontroller,referencethevaluespublishedintheLogix5000ControllersExecutionTimeandMemoryUseReferenceManual,publication.Lgx00106477
EnhancementswithRevision16.80SystemComponentEnhancement1756-L61,1756-L62,1756-L63,1756-L63XT,1756-L64SupportforredundantcontrollerusewithalarmfeaturesofFactoryTalkAlarmsandEventssoftware.ThisredundancyfirmwarerevisionprovidessupportforalarmsassupportedbyFactoryTalkAlarmsandEventssoftware.Alarmscannowbeembeddedinthecontrollerwithtwonewinstructions,ALMDandALMA,availablein
RSLogix5000software.Thesedigitalandanalogalarminstructionsarefullyself-contained.
Supportforredundantcontrollerusewithequipmentphases.
ThisredundancyfirmwarerevisionprovidessupportforequipmentphasesthatcanbeimplementedbyusingFactoryTalkBatchsoftwareandtheRSLogix5000PhaseManagerfeature.SeetheApplicationNotesonformoreinformationaboutusingaredundantsystemandequipmentphases.
Publication1756-RN650D-EN-E-February2010
6ControlLogixEnhancedRedundancySystem,Revision16.81
1756-RM,1756-RMXTAuto-qualificationandsynchronizationprocessesofthe1756-RMmodulearestoppedafterachassispairfirstfailsto
synchronize.
Inpreviousfirmwarerevisions,iftheAuto-QualificationparameterissettoAlwaysandthecontrollerinthesecondarychassisfaulted,oracommunicationmodulewasremovedfromthechassis,the1756-RMmodulewouldcontinuouslyattempttoqualifytheredundantchassis.Asaresultofthecontinuousattemptstoqualify,theeventlogsbecamefilledwithsynchronizationfailureevents,thusmakingtheoriginatingfaultmoredifficulttotroubleshoot.
Withthisfirmwareenhancement,the1756-RMmodulestopsauto-qualificationandsynchronizationattemptsafterthefirstfaultoccurs.Thismakestroubleshootingtheoriginalfaulteasier.
Lgx00080574
Synchronizationfailurereportsenhancedbyadding’PartnerModulenotFound’cause.
Inpreviousrevisions,ifsynchronizationfailedduetopartnermodulesbeingatincompatiblefirmwarerevisionsorasecondarymodulewasnotinstalledorpowered,thenfailurewasindicatedbythesamecausestatementinthesynchronizationlogoftheRMCT.Forbothtypesoffailures,’ModulePairIncompatible’wasindicatedasthecause.Withthisfirmwarerevision,the1756-RMmodulecandifferentiatebetweenpartnerincompatibilitiesandamissingsecondarymodule.TheRMCTindicatesamissingsecondarymodulebystating’PartnerModulenotFound’intheCausecolumnoftheRecentSynchronizationAttemptslog.
Lgx00083165
EnhancementswithRevision16.80
SystemComponent
EnhancementModuleisnotinstalledorpoweredinchassis
Modulesareatdifferentfirmwarerevisions.
Publication1756-RN650D-EN-E-February2010
ControlLogixEnhancedRedundancySystem,Revision16.817
EnhancementswithRevision16.80
Publication1756-RN650D-EN-E-February2010
8ControlLogixEnhancedRedundancySystem,Revision16.81
EnhancementswithRevision16.54
Theseenhancementswereprovidedwithenhancedredundancyfirmware
revision16.54.
EnhancementsProvidedwithRevision16.54SystemComponent
Description1756-L61,1756-L62,1756-L63,1756-L63XT,1756-L64Firmwarerevision16.54providesredundancysupportforcontrollerprogrammingwithAdd-OnInstructions.SynchronizationpointsforprogramswithintheRSLogix5000projectcanbeconfigured.Redundancyfirm