装置布置工程规定.docx
《装置布置工程规定.docx》由会员分享,可在线阅读,更多相关《装置布置工程规定.docx(16页珍藏版)》请在冰点文库上搜索。
装置布置工程规定
北京中寰工程项目管理有限公司
BeijingZhonghuanEngineering&ProjectManagementCo.,Ltd.
项目名称:
PhiferLTDNingboPlant
飞佛特种纺织品(宁波)有限公司项目
装置名称:
资质等级:
乙级
证书编号:
011053-sy
文件号
XXXXX
ENGINEERINGSPECIFICATION
FOR
PLANTLAYOUT
装置布置工程规定
C0
FORCONSTRUCTION
王生勇
修改
REV
说明
DESCRIPTION
编制
PRE’D
校核
CHK’D
审核
APP’D
审定
AUTH’D
项目经理
PROJ.MAN
日期
DATE
TableofContents
1.General3
2.GeneralConsideration3
3.SiteLayout5
4.ArrangementOfEquipment6
5.Pipeways8
6.Accessways8
7.SafetyDistanceGuide9
(中文)
1.概述11
2.总则11
3.现场布置12
4.设备布置13
5.管廊14
6.通道14
7.安全距离导则15
1.GENERAL
1.1Scope
(1)Thisspecificationcoverstherequirementsofthelayoutofprocessunitandassociatedfacilitiesandalsoforthespacingofequipmentandstructurestoprovideforsafeandeasyoperation,maintenanceandconstructioninPhiferLTDNingboPlant.
(2)Clearanceandaccessforoperationandmaintenanceofequipmentfurnishedasaregularpartofproprietaryequipment(orpackageunit)maybeinaccordancewiththeequipmentmanufacturerstandards.
1.2CodesandStandards
Thefollowingcodesandstandardsshallbeappliedtothisspecification.
(1)GB50160-92:
FirePreventionCodeofPetrolChemicalEnterpriseDesign
(2)HG20546-92:
DesignStandardEquipmentLayoutforChemicalPlant
1.3RelatedEngineeringSpecifications
5084-000-00-PP0202:
EngineeringSpecificationforPipingDesign
1.4Units
Unlessotherwisespecified,metric,Celsiusunitsshallbeappliedasthemeasurementsystem.Nominalsizesofpipingshallbeinaccordancewithinchsystem(").
2.GENERALCONSIDERATIONS
2.1SiteConditions
Forlayoutstudy,followingsiteconditionsshallbetakenintoaccount.
(1)Geologicalcondition
(2)Winddirection
(3)Environmentconditions
(4)Utilities
(5)Climaticconditions
2.2LayoutPhilosophy
2.2.1SafetyConsiderations
(1)Equipmentwhichcouldbeconsideredaspossiblesourcesofhazardshouldbegroupedtogetherand,wherepossible,locatedseparatelyfromotherareas.
(2)Theoccupiedbuildingssuchascontrolroom,laboratoryshallbelocatedinnon-hazardousarea.
(3)Roadsshallbearrangedtorealizeeasyaccessoffireengineanddeadendshouldbeavoided.
2.2.2OperationalConsiderations
(1)Forequipmentrequiringfrequentattendancebyoperatingpersonnel,theshortestorthemostdirectroutefromthecontrolroomshouldbeconsidered.
(2)Controlroomandswitchroomshallbeadjacenttotheroadtokeepeasyaccessandemergencypedestrianescape.
2.2.3MaintenanceConsiderations
(1)Fortheequipmentrequiringreplacementofinternals,spentcatalyst,etc.orfrequentinternalcleaning,themaintenanceworkareashallbeconsidered.
(2)Whenthemobilecraneisrequiredformaintenanceofequipmentsuchasheatexchangers,ejectors,filters,etc.,accessforthecraneshallbeconsidered.
2.2.4MaterialFlowConsiderations
Equipmentshallbearrangedtobesuitedforthematerialflowinordertoprovideaneconomicalfacility,safeandeasyoperationandmaintenance.
2.2.5EconomicConsiderations
Compactnessandintegratedarrangementofunitsandequipmentshallbeconsidered.
2.2.6Appearance
(1)Buildings,structuresandgroupsofequipmentshouldformaneat,symmetricalbalancedlayout.
(2)Pipewaysshouldbelaidoutinanorderlyarrangementasthebackboneoftheplant.
3.SITELAYOUT
3.1DescriptionofFacilities
Thesiteareashallbedividedintofollowingunit/facilitiesareabyroadsand/orfences.
(1)Processunitarea(On-site)
(2)Associatedfacilitiesarea
3.2LayoutofProcessUnitArea
3.2.1General
(1)Theprimaryconsiderationinarrangementofunitandequipmentinon-siteistoprovideasafeandeasyoperationandmaintenancewithsatisfyingprocessrequirements,suchasgravityflowforliquidorsolids.
(2)Thearrangementofunitandequipmentshouldpreferablybecompactandintegrated.Andalso,thearrangementshouldrealizeeaseofidentifyingandisolatingaffectedareasfromtherestintheeventofanemergency.
3.2.2LayoutofMainprocessUnit
(1)WhenProcessunitconsistsofsomesection,andwherethereisamaterialflowbetweenindividualsection,thelayoutofsectionshouldbe,asfaras,economicalinalogicalorderofflow.
(2)Sectionconsideredasaspecialtoxichazardorhavingthecapacitytoproduceamajorflammablevaporreleaseshallbelocatedtominimizetheeffectofanyinadvertentreleaseoffluidonpersonnelwithinthesiteandalsoonactivitiesoutsidethesiteboundary.Theeffectoflocaltopographicalfeaturesandprevailingwindshallbeconsideredinselectingthemostsuitablelocation.
3.2.3LayoutofStorageTanks
(1)General
Allstoragetanksshallbegroupedandlocatedtogether.
(2)TankSpacing
Forfixedorfloatingrooftankscontainingflammableorcombustibleliquid,thespacingbetweentankandtank/otherobjectshallbeinaccordancewithGB50160-92.
(3)TankDikedesign
(a)FixedorfloatingrooftankscontainingflammableorcombustibleliquidshallbesurroundedbydikeinaccordancewithGB50160-92.
(b)Whererequired,intermediatedikeswillbeprovidedfordividingtanksintosmallgroups.
3.2.4ControlBuilding
(1)Controlbuildingshouldbelocatednearthemainroadwithkeepingsafetydistancefromotherfacilities.
(2)Controlbuildingshallbelocatednearbymainprocessunit,butinnon-hazardousarea.
(3)Controlbuildingshallbelocatedtoallowunobstructedemergencypedestrianescapetosafelocation.
Theseescaperoutesshallnotcrossanyfireriskareaandshouldnotpassthroughamainprocessunitarea.
4.ARRANGEMENTOFEQUIPMENT
4.1General
(1)Equipmentshouldbearranged,asfaraseconomical,inalogicalorderofmaterialflow.
(2)Equipmentandstructuresshallbearrangedtopermitmobilecraneaccesstocompressorsandmajorequipmentpartsnotprovidedwithbuilt-inmaintenancefacilities.
(3)Equipmentcontainingstrongacidoralkalis,certaintoxicorothercorrosivechemicalsshouldbegroupedtogether,providedthisispracticalandeconomical.
(4)Equipmentandstructuresshallbearrangedtopermitequipmenttakingoutforexchangeandmaintenance.
4.2Pumps
(1)Pumpsshallbelocatedascloseaspossibletothesuctionvesselsinordertorealizetheshortestpossiblerunofsuctionlines.
(2)Pumpsshallbelocatedneardrainagetrench,ifpossible.
(3)Pumpsshallgenerallybeplacedongroundandadequateclearanceshallbeprovidedaroundthepump,motorandtheirauxiliaryunit.
(4)Pumpsshouldpreferablybelocatedunderoverheadpiperackinordertosavetherequiredunitarea.
(5)Pumpsshallgenerallybelinedupparalleltopiperacktomaintainauniformityoflocation.
4.3HeatExchangers
(1)Ingeneral,heatexchangersshouldbelocatedclosetotherespectiveequipment.
(2)Indecidingthelocationofheatexchangers,requiredareaforthemaintenanceshallalsobeconsideredsoasnottoprojectintoanescaperouteoranyroadwithunrestrictedvehicleaccess.
(3)Heatexchangerswithremovabletubebundlesshouldbelocatedtorealizetubebundleremovalworks.
(4)Spaceshallbeprovidedforwithdrawingbundles,removingandtemporarilystoringchannelcover.
(5)Heatexchangerswithoutremovabletubebundlesshallbearrangedsothattheycanreadilybedismantledforcleaningandmaintenance.
5.PIPEWAYS
5.1General
Pipewaysshallgenerallybeoverheadpiperacksintheplant.Overheadpiperacksshallgenerallynotcontainmorethanfourlevelsofpiping.
5.2Height
Heightofthelowestdecksofpiperacksshallbedeterminedtosatisfythefollowingconditions.
(1)Tokeeptheoverheadclearanceforhangingequipment(pumps,channelcoversofheatexchangers,etc.)toberemovedforthemaintenance,ifrequired.
(2)Tokeeppipingspacetobeconnectedtovesselsandheatexchangersinstalledunderpiperack.
(3)Tokeepaccessspaceunderpiperackformaintenancevehiclesuchasaforklift,ifrequired.
(4)Tokeepaccessspaceforautomobiles.
5.3FutureSpace
A25%ofsparespaceforfutureinstallationsshallbeprovidedforallpiperackswithintheplant,Forthemultilevelpiperacks,thesaidpercentageisbasedonthetotalwidthofalllevels,butnotonthewidthofeachlevel.
6.ACCESSWAYS
6.1General
(1)Foroperationandmaintenanceoffacilities,operatoraccesswaysshallbeplanned.
(2)Pedestrianaccessforfirefightingandescapingatemergencyfrom/toallroadsaroundtheplantshallalsobeconsidered.
6.2Width
Theminimumwidthofaccesswaysshallbeasfollows.
(1)Accesswaysatgrade:
0.8m
(2)Elevatedaccesswaysandstairways:
0.75m
(3)Walkwaysonpiperacks:
0.6m
(4)Overbridgesacrosspipesleepers:
0.6m
6.3OverheadClearance
Theoverheadclearanceaboveaccessways,stairwaysandwalkways(onpiperack)shallgenerallybeminimum2.5m.
Theareaswhichrequireisverylimitedaccessofpersonnelmaybeprovidedwith2.1moverheadclearance.
6.4AdditionalRequirementsforSafetyAccess
6.4.1Platforms
(1)Toeplatedshallbeprovidedontheedgesofallplatformareasandaroundplatformopenings,exceptattheplatformentranceandexitlocation.
(2)Standardhandrailshallbeprovidedonopensideofallplatformareasandstairways.
6.4.2Stairways
Theminimumwidthofstairwaysshallbe750mm.
6.4.3Ladders
Raillessladdersshallnotbeapplied.
7.SAFETYDISTANCEGUIDE
7.1General
(1)Safetydistancefromcertainfacilitiesorequipmentintheplanttopublicbuildings,roads,etc.,shallgenerallybeinaccordancewiththe