Check of electrical specification Rev4Word格式文档下载.docx
《Check of electrical specification Rev4Word格式文档下载.docx》由会员分享,可在线阅读,更多相关《Check of electrical specification Rev4Word格式文档下载.docx(34页珍藏版)》请在冰点文库上搜索。
1.5ControlandSignalCircuits5
1.6ArrangementofElectricalEquipment5
1.7ControlDevices6
1.8Cables,LeadsandConductors7
1.9Wiring7
1.10ElectricMotors7
2PROFIBUS9
2.1Checkofdocumentation9
2.2Visualinspection9
2.3Wiringtest(PROFtestII)orequal9
2.4Levelmeasurement(PROFviewXL)orequal9
2.5Shieldcurrentmeasurement(CHB3)orequal9
2.6Logicalassessment(PBScope)orequal9
3MachineSoftware11
3.1General11
3.2IPCBasicSoftware/SoftwareSettings11
3.3PLCSoftware12
3.4ProcessVisualizationSystem13
3.5Interfaces14
4ElectricalMachineDocumentation15
4.1General15
4.2Hardware15
4.3Software16
1
ElectricalMachineEquipment/Installation
Yes
No
N.A.
Remarks
1.1General
1.1.1
EquipmentfollowsSpecification?
Typeofcontrolsystem,PLC-CPU,IPC,In-/Outputcards,drives,motorareexecutedasspecifiedinElectricalPartList
1.1.2
Latestrequestedmodificationsareintegrated?
1.1.3
Allsafetyandwarningsignscomplete?
1.1.4
Areinscriptionlabelsandnameplatesinlocallanguage?
E.g.mainoperatorpanel,pushbuttonpanels
1.1.5
HasthemachineEthernetTCP/IPcapability?
1.1.6
Allnameplatesfixedineasilyreadablelocation?
1.1.7
Functionaltestincl.Emergency-STOP/safetycircuit?
1.1.8
Paintcompleteandfollowingspec.?
StandardcabinetcolourRAL7035–lightgrey
1.1.9
Allnecessaryconnectionpointsfortransportdone?
1.1.10
Allguardsmounted?
1.1.11
Allcablechannelsclosed?
1.2NominalVoltages
1.2.1
PowerSupply
1.2.1.1
Ispowersupplyaccordingspecification?
▪Voltage
▪Frequency
▪Netpowerconfiguration(e.gTN-S/TN-C)
▪BackupsystemUPS(central/individual)
Pleasenotedata
1.2.1.2
AreallmachinepartsconnectedtoEarthingsystem?
1.2.2
AuxiliaryVoltage
1.2.2.1
Is24Vcontrolvoltageusedforelectroniccontrols?
E.g.pneumatic/hydraulicvalves,PLCIn-/Output,relay,contactoretc.
1.3Inscription,Identification,Marking
1.3.1
IdentificationofElements
1.3.1.1
Doallelectricaldeviceshaveidentificationmarksaccordingdocumentation?
1.3.1..2
Doalloutsideinstallationshaveengravedorembossedinscriptionplates?
Doublemarkingrequired(machineframe+sensor)
E.g.proximityswitch,motor,valveetc.
1.3.1.3
Doallcabinetpartshaveinscriptionplates?
Doublemarkingrequired(plate+part)
E.g.contactor,fuse,driveetc.
1.3.2
IdentificationofTerminalBoxes
1.3.2.1
Doallterminalboxeshaveidentificationplatesatthefixpartofthebox?
Doallinsideboxesexistingterminalblockshaveidentificationplates?
1.3.3
Identification,MarkingofCablesandWires
1.3.3.1
Dooutsidecableshavelabelsonbothends?
1.3.3.2
Aremulticonductorcablesofnumberedtype?
1.3.3.3
Arewireandcablelabelsmachineprintedandofoilandwaterresistanttype?
1.3.3.4
Doallwireshavesinglewiremarking?
Devicereferencedesignationwithconnectingpointnumber
E.g.-55X2:
7,+F-81K5:
4
1.4ProtectiveandEnclosureMeasures
1.4.1
Doallmotorshaveoverloadprotection?
1.4.2
Isequipmentwithoverloadprotectionselfstartingprevented?
1.4.3
DoplugcircuitsandsocketoutletshavefaultcurrentbreakerdevicesonIn=30mA?
1.4.4
Domushroom-andpull-cordemergencystopswitcheslockinpositionafteroperation?
1.4.5
AremainswitcheslockableonlyinOFFposition?
1.4.6
Isdegreeofprotectionaccordingtospecification?
1.5ControlandSignalCircuits
1.5.1
Transformer
1.5.1.1
Arecontroltransformersofminimumtwocoiltype?
1.5.1.2
Iscontroltransformersecondarywindingconnectedtoprotectiveconductorsystem?
1.5.2
Auxiliarycircuits
1.5.2.1
Isthecontrolvoltagesystemappropriatelyseparatedbyfusesinfunctionalgroups?
1.6ArrangementofElectricalEquipment
1.6.1
ConditionofElements
1.6.1.1
Isallelectricequipmentinoriginalconditionandwithoutanymodification?
1.6.2
ElectricalCabinet
1.6.2.1
GeneralArrangement
1.6.2.1.1
Arecabinetsequippedwithringlugsfortransport?
1.6.2.1.2
Arecabinetdoorleafswithmax.widthof600mmusedwithopeningangelsofatleast165°
?
1.6.2.1.3
ArecabinetdoorsequippedwithRittal–EGOFORMS–Lockingsystem?
1.6.2.1.4
Arenodevicesandsub-assembliespositionedonbackorsidewalls?
1.6.2.1.5
Arepocketsandcircuitdiagrampanels,sizeA3fittedoninsideofdoor?
1.6.2.1.6
Isatleast20%spaceforfuturerequirements,(extendedtodevicesofindividualfunctiongroups,terminalblocks,cableductsandprogrammemory),foreseen?
1.6.2.1.7
Docabinetsectionshavecabinet-fluorescentlampsanddoor-positionswitcheswhicharestillinoperationafterswitchingoffmainswitch?
1.6.2.2
CabinetCooling
1.6.2.2.1
Iscabinetcoolingsystemautomaticallyinterruptedifthecabinetdoorsareopened?
1.6.2.2.2
Functionaltestofcabinetcooling?
1.7ControlDevices
1.7.1
ContinuousOperation
1.7.1.1
Areproximityswitchesincaseofhighswitchingfrequenciesused?
1.7.1.2
Arelimitswitchesincaseofsafetyrelevantfunctionsused?
1.7.2
Supply,Connection,Indication
1.7.2.1
Areallvalves,pressureswitches,proximityswitches,photocellsofplugtype
1.7.2.2
Areallposition-andproximityswitches,valvesetc.equippedwithLEDindicatoronplugshowingoperationstatusandpowersupply?
1.7.2.3
Arelimitingelementsinstalledtopreventagainstexcessivevoltages?
1.8Cables,LeadsandConductors
1.8.1
Arecontrolcablesofflexibletypeoratleastmultistrandedconductorcables?
1.8.2
Arecableswhicharesubjecttomovementduringoperationofhighflexibletypespeciallyconstructedforthispurpose?
1.8.3
AresignalandpowercablesseparatedfromACdrivecablesinindependentcabletrays,orminimumseparatedbypartition?
1.8.4
Arefieldbusandcomputercablesinstalledaccordingtosupplierspecification?
1.9Wiring
1.9.1
IsthecolourcodingforwiresaccordingtoIEC60204-1?
1.9.2
Arenoterminalsorterminalconnectorsusedinwiringchannels?
1.9.3
Isonlyonewireconnectedinoneconnectionpointofterminalblock?
1.9.4
Areterminalswithdifferentpotentialseparated?
1.9.5
Areallconnectionsconnectedviaterminalorplugs?
1.9.6
Areallconductorends,incaseofscrewterminalsequippedwithcableshoesorequivalent?
1.9.7
Arealljunctionboxesapprovedbrandandmetaltype?
1.9.8
Arenoswitchingdevicesaccommodatedinterminalboxes?
1.9.9
Doallcablesenterboxeswithmetric-screwedcableglandsandaretheymetallictype?
1.9.10
Nometalcableglandsareallowedtobescrewedintoplastichousings
1.9.11
Areallwiresandcablesinsidecabinetinstalledinwiringchannels?
1.9.12
Arealloutsidewiringchannelsofmetaltype?
1.10ElectricMotors
1.10.1
Areallthreephasemotorsofmaintenancefreetype?
1.10.2
Arealldirectoperatedthreephasemotorsrated7,5kWandmoreincaseofstartupunderloadarestartedbysoft-starter?
1.10.3
ACgearmotorsaccordingspecification?
▪SEWtype
▪IntegratedplugconnectorIS(<
size132S/5,5KW)
▪ThermistorprotectionTFincaseoffrequencycontrol
1.10.4
Ismotorbrakevoltageaccordingtospecification?
1.10.5
Areallmarkingsindicatingfunctions,arrowsindicatingdirectionandopen/closelabelsaffixedexternallytothemachineandsecuredagainstdamage?
Remarks:
____________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________
2PROFIBUS
N/A
2.1Checkofdocumentation
2.1.1
Bus-topologyexisting=ok
2.1.2
Informationintopologyplancorrect=ok
Remark
2.2Visualinspection
2.2.1
Detailsintopologyplanareequaltoreality=ok
2.2.2
Cableroutinghasnovisualfailures=ok
2.2.3
Cableshieldinghasnovisualfailuresordefects,
Propergroundingdone=ok
2.3Wiringtest(PROFtestII)orequal
2.3.1
TestwithoutBus-ter